Heating systems — low-pressure pump protection (prevents dry running). Cooling systems — low-pressure protection for refrigerant/water. Water supply — hydrophore pump start/stop switch. Delivery across the EU.
| Parameter | Value |
|---|---|
| Code | ERE000005 |
| Type | Mechanical pressure switch |
| Pressure range | −0.2 … 7.5 bar |
| Differential | 0.4-1.5 bar |
| Max working pressure | 17 bar |
| Contact type | SPDT (single-pole double-throw) |
| Electrical rating | 10 A / 400 V AC (resistive) |
| Pressure connection | G 1/4" or 7/16" UNF |
| Protection class | IP 44 |
| Ambient T | −40 → +65 °C |
KP35 is available with manual-reset and auto-reset options. For safety-critical duties choose manual reset — the operator must acknowledge the trip before restarting.
Official Danfoss catalog: store.danfoss.com/KP35
No — KP35 is a low-pressure (LP) switch. HP protection uses other KP models (KP1, KP2) or the MBC/CAS series.
Manual reset — operator must reset the switch after a trip (safety duty). Auto reset — resets itself when pressure returns to normal (control duty).