After Alfa P-Scale CIP cleaning, the spent acidic solution cannot be discharged to sewer directly — the pH is too low (2-4) and it contains dissolved calcium and inhibitor residues. P-Neutra is added gradually to the used P-Scale solution while circulating through the exchanger until pH reaches 6-8. During the reaction, insoluble salts form and are readily flushed with water. This two-stage process ensures safe disposal and a fully cleaned exchanger.
| Parameter | Value |
|---|---|
| Code | 3284000601-03 |
| Manufacturer | Alfa Laval |
| Product | Alfa P-Neutra (alkaline powder neutraliser) |
| Purpose | Neutralising P-Scale acid after CIP procedure |
| Target pH | 6-8 (neutral, safe for sewer) |
| Form | Powder (added gradually to spent P-Scale solution) |
| Used with | Alfa P-Scale (SKU 3284000602) |
| Application method | Circulate via CIP unit until neutral pH |
| Procedure time | 1-2 h (depending on initial acid concentration) |
| Plate compatibility | Stainless steel, titanium (lab-verified by Alfa Laval) |
| Gasket compatibility | EPDM, NBR — lab-verified |
| Disposal after neutralisation | Sanitary sewer (flush with water) |
Official Alfa Laval datasheet: alfalaval.com/P-Neutra PPS00005en
No. P-Neutra is only a neutralising agent. For inorganic scale (calcium carbonate), an acid cleaner (P-Scale) is required. For organic fouling — Alfa Laval offers a separate Alfa Descaler / Alfa Clean range.
Depends on P-Scale quantity used and final pH measurement. Typical ratio — ~1:1 by mass with P-Scale, but exact quantity is set dynamically by measuring pH.
The alkaline powder is skin and eye irritant. Goggles, gloves, and lab coat are required. In poorly ventilated area, may irritate respiratory tract.
Universal litmus strips (see Amegata SKU PND50-975-84 — pH 0-12 strips) or a digital pH meter. Recommended measurement every 15 min during the procedure.
No. The neutralised solution must be disposed of (sewer). A new CIP procedure requires a fresh P-Scale + P-Neutra pair.