Diaphragm safety relief valve protecting closed water heaters (hot water cylinders) against overpressure per DIN 4753. The 8 bar opening pressure must not exceed the permissible working pressure of the protected water heater.
| Parameter | Value |
|---|---|
| Code | 10004726 |
| Series | Watts SVW |
| Type | Diaphragm safety relief valve for water heaters (DIN 4753) |
| Opening pressure | 8 bar |
| Inlet thread | 3/4" (internal) |
| Outlet thread | 1" (internal) |
| Max working temperature | 110 °C |
| Media | Water |
| Body material | Brass CW617N |
| Diaphragm | EPDM |
| Certification | TÜV, DIN 4753, PED 2014/68/EU |
| Installation position | Vertical, spring upwards |
The valve size is chosen according to the water heater output and volume using the manufacturer (Watts) table and DIN 4753; confirm the exact match in the Watts datasheet.
Watts manufacturer's catalogue: wattswater.eu
Most common — mineral deposits on the seat from repeated actuation, or corrosion in a valve that has never operated. Prevention: annual manual opening test (lever pulled fully).