DHW temperature control in small substations and single-family houses. The thermostat sensor is threaded into the DHW outlet of the plate heat exchanger — it senses hot-water temperature and modulates the primary flow. A power-free solution suitable for retrofit and small substation projects. Delivery across the EU.
| Parameter | Value |
|---|---|
| Code | 003N5111 |
| Type | Self-acting thermostatic valve |
| DN | 15 |
| Kvs | 1.9 m³/h |
| Connection | G 3/4" male thread |
| Setting range | 20-60 °C (standard head) |
| PN | 16 bar |
| Max media temperature | 130 °C |
| Capillary tube | 2 m (integrated) |
| Body material | Dezincification-resistant (DZR) brass (BS 2872 / CZ132) |
AVTB has no electronic feedback — under sudden DHW demand (shower) response may lag due to sensor thermal inertia. A modern alternative is electronic PID control via ECL Comfort + AMV + VS2/VF valve.
Danfoss manufacturer catalog: store.danfoss.com/003N5111
No. AVTB is a self-acting controller: the thermostatic actuator (bellows, impulse tube and sensor) mechanically opens/closes the valve according to temperature.
≥ 55 °C DHW is typically recommended for Legionella prevention (check the applicable regulations). Set via the dial on the head.
Into the DHW outlet pipe of the plate heat exchanger (towards the consumer). The capillary tube allows placing the sensor up to 2 m from the valve.