TL;DR: Watts SVW 6 1" — higher-capacity diaphragm safety relief valve for closed heating systems up to 6 bar design pressure. 1" inlet and 1 1/4" outlet provide sufficient discharge capacity for higher-output boilers and central multi-family boiler rooms.
  • Opening pressure: 6 bar (fixed)
  • Inlet connection: 1" internal thread
  • Certification: TÜV per DIN EN 1268
  • Typical boiler output: up to ~250 kW (per DIN 4751 table)

Where Watts SVW 6 1" is used

Applied in higher-output closed heating systems — central boiler rooms of multi-family buildings, commercial premises, industrial buildings where combined generator output exceeds 100 kW. 1" inlet connects directly to trunk pipework without adapters; enlarged 1 1/4" outlet ensures discharge capacity during sudden overpressure events.

Technical specifications

Parameter Value
Code10004749
SeriesWatts SVW
TypeDiaphragm safety relief valve (closed systems)
Opening pressure6 bar
Inlet thread1" (internal)
Outlet thread1 1/4" (internal)
Max working temperature120 °C
MediaHeating system water, glycol solution up to 30 %
Body materialDZR brass
DiaphragmEPDM
CertificationTÜV, DIN EN 1268, PED 2014/68/EU
Installation positionVertical, spring upwards

Sizing by boiler output

Watts SVW 6 1" per DIN 4751 typically covers up to ~250 kW generator output (with 6 bar opening pressure). Exact sizing is done by the designer using Watts catalogue capacity tables, factoring generator type (gas / solid fuel / heat pump), system layout and local regulations.

Designer note: safety valve size is chosen not by the boiler connection size, but by the capacity table. A common mistake is fitting a 3/4" valve to a 25 kW gas boiler with a 1" outlet just because the boiler has a 3/4" tapping — this can undersize the discharge under a sudden overpressure event.

When to choose SVW 6 1" over SVW 6 3/4"

  • Multi-family central boiler rooms with combined heating load up to ~250 kW
  • Commercial buildings with mid-capacity heating systems
  • Industrial process circuits (process heating up to 6 bar)
  • When the trunk pipework is 1" — reduces fitting count

B2B delivery and logistics via Amegata.lt

  • 24-hour delivery across the EU (from our warehouse in Vilnius)
  • Competitive B2B pricing — often below market average
  • 30-day payment terms for companies (per contract)
  • Free technical consultation for valve sizing

Official Watts catalogue: wattswater.eu

Frequently asked questions

When is 1" size required and when is 3/4" enough?

The decision depends on generator output, not pipework size. Rule of thumb: up to ~100 kW — 3/4" (SVW 6 3/4"), 100-250 kW — 1" (SVW 6 1"), above 250 kW — larger versions or parallel safety valve groups.

Can several SVW be piped in parallel?

Yes. In high-output systems (>250 kW) TÜV allows parallel installation — combined nominal discharge capacity must not be less than that required by the generator output.

What is the difference between SVW and Watts SVE?

SVW — safety valve for closed heating systems (closed loop with expansion vessel). SVE — safety valve for domestic hot water storage cylinders (DHW) — with different intermediate characteristics and potable-water certifications.

Is inlet / outlet isolation (shut-off) required?

No. EN 12828 and DIN 4751 prohibit any shut-off device (ball valve, filter, check valve) between the boiler and the safety valve. The connection must be direct and non-blockable.