For high-rise residential blocks and commercial buildings with heating systems designed up to 10 bar. Typical cases — 10+ storey buildings with central boiler rooms where the hydrostatic column alone reaches 5-6 bar; industrial buildings with high-temperature heating; district-connected systems with elevated working pressure. 1" inlet minimises pressure drop across the valve and ensures fast response at the opening point.
| Parameter | Value |
|---|---|
| Code | 10004751 |
| Series | Watts SVW |
| Type | Diaphragm safety relief valve (closed systems) |
| Opening pressure | 8 bar |
| Inlet thread | 1" (internal) |
| Outlet thread | 1 1/4" (internal) |
| Max working temperature | 120 °C |
| Media | Heating system water, glycol solution up to 30 % |
| Body material | DZR brass |
| Diaphragm | EPDM |
| Certification | TÜV, DIN EN 1268, PED 2014/68/EU |
| Installation position | Vertical, spring upwards |
Watts SVW 8 1" per DIN 4751 typically covers up to ~200 kW generator output at 8 bar opening pressure. Higher loads require a specialised safety valve group or a larger DN valve (e.g. SVW 8 1 1/4" — larger model in the same series).
Official Watts catalogue: wattswater.eu
Assess hydrostatic column (each 10 m adds ~1 bar static pressure) + working pressure on the lowest floor + expansion vessel precharge. Total operating pressure on the lowest floor must not exceed ~70 % of the valve opening pressure. For a 15-storey block (~4.5 bar static + 1 bar working) an 8 bar valve is recommended.
Technically yes, but uneconomical and potentially unsafe: if the system is designed only for 6 bar, components (expansion vessel) may fail before the valve triggers. Choose a valve whose opening pressure matches the weakest component's max working pressure (minus a safety margin).
DIN 4751-1 requires: (1) valve mounted as close to the heat generator as possible, (2) no shut-off devices between boiler and valve, (3) discharge open/visible, (4) discharge pipe length and bends limited per the capacity table, (5) annual functional testing.
Not necessarily. Expansion vessels typically last 8-12 years, safety valves 10-15 years. Replace when a defect is visible or during a larger overhaul (boiler room refurbishment).