This 110-plate brazed heat exchanger with H (high) chevron angle and 2-pass (2S) configuration is typically chosen for domestic hot water (DHW) primary circuits in multi-family substations (primary side — district heating network, secondary side — DHW). The 2-pass configuration with 6 connections efficiently maintains the logarithmic mean temperature difference (LMTD) under asymmetric DHW loads (e.g., 70/40 °C → 10/55 °C). The compact housing (123 × 286 mm base × height) fits even in tight technical rooms.
| Parameter | Value |
|---|---|
| Code | 0203-0722 |
| Series | Hexonic LB31 |
| Model | LB31-110H-2S-5/4 |
| Number of plates | 110 |
| Configuration | 2-pass (2S), 6 connections |
| Nominal pressure (PN) | 30 bar (3.0 MPa) |
| Connection | G 1¼" (5/4) external thread |
| Plate material | Stainless steel AISI 316L |
| Brazing material | Copper |
| Working temperature range | −195 °C … +230 °C |
| Dimensions (W × D × H) | 123 × 268.5 × 286 mm (W × D × H) |
| Weight (approx.) | ~14.14 kg |
| Construction | Vacuum-furnace brazed, hermetic (gasket-free) |
| Media | Water, inhibited propylene and ethylene glycol solutions at standard concentrations; other media — consult the manufacturer |
Capacity depends on flow rate, ΔT and logarithmic mean temperature difference (LMTD). General formula: P = Q × ΔT × 1.163 (kW, where Q — m³/h, ΔT — °C).
Illustrative calculation, not this model's capacity. Example for typical heating duty (primary 90/70 °C → secondary 65/40 °C): at Q = 3.6 m³/h and effective ΔT ≈ 25 °C → P ≈ 105 kW.
The letter denotes the plate chevron angle: "H" — high angle (higher heat transfer coefficient, higher pressure drop), (no letter — standard profile), "L" — low (lower Δp, suits higher flow rates).
Yes. Hexonic L-series copper-brazed exchangers are compatible with ethylene glycol and propylene glycol solutions at standard concentrations, when appropriate inhibitors are used. For DHW systems, only potable-grade fluids are allowed.
Brazed gasket-free construction requires no periodic disassembly maintenance. Recommended only CIP (Clean-in-Place) flushing periodically if fouling signs appear (rising pressure drop or falling heat transfer). Use only manufacturer-approved alkaline and acid cleaning agents; mechanical cleaning (brushes, scrapers) and chlorinated agents must not be used.g., citric, sulfamic acid) followed by neutralization and rinsing.
Not in all cases. Hexonic states that the standard copper-brazed L series should not be treated as a universally suitable solution for direct contact with potable water — acceptability depends on local requirements and approvals. For potable water Hexonic recommends SafePLATE (double-wall design) or the all-stainless-steel LUNA series.
In some regions, district-heating water contains elevated chlorides or ammonia — in such systems, copper brazing may shorten the service life of the exchanger. In these cases we recommend the Danfoss XB CoResist series. For hard water with elevated Ca/Mg carbonate content, limescale gradually builds up on the plates and reduces heat-transfer efficiency; for such systems gasketed (plate-and-frame) exchangers are preferable, as they can be periodically opened for mechanical or CIP cleaning. Contact us — we will select the model best suited to your water conditions.