The 60-plate Hexonic LB60 exchanger is typically selected for: medium-to-large capacity heat substations, cooling systems primary/secondary loop separation, process heat recovery, solar and geothermal system separation. The brazed gasket-free construction requires no periodic disassembly maintenance that gasketed exchangers would need. The compact housing (plate 538 × 123 mm, depth 152 mm) fits even in small technical rooms.
| Parameter | Value |
|---|---|
| Code | 0205-0096 |
| Series | Hexonic LB60 |
| Model | LB60-60-5/4 |
| Number of plates | 60 |
| Plate profile | Standard |
| Passes | 1 (1-pass, 4 connections) |
| Nominal pressure (PN) | 30 bar |
| Max working temperature | 230 °C |
| Min working temperature | -195 °C |
| Connection | G 5/4" (1-1/4") external thread (K1-K4) |
| Plate material | Stainless steel AISI 316L (1.4404) |
| Brazing filler | Copper (Cu) |
| Plate dimensions | 538 × 123 mm |
| Unit depth (F) | ~152.0 mm (formula: 11 + 2.35 × N, N = 60) |
| Weight | ~15.1 kg |
| Construction | Brazed, hermetic (gasket-free) |
| Media | Water, inhibited propylene and ethylene glycol solutions at standard concentrations; other media — consult the manufacturer |
Capacity depends on flow rate, ΔT and logarithmic mean temperature difference (LMTD). General formula: P = Q × ΔT × 1.163 (kW, Q m³/h, ΔT °C).
Illustrative calculation, not this model's capacity. Example for heating mode (primary 90/70 °C → secondary 65/40 °C): at Q ≈ 11.0 m³/h and effective ΔT ≈ 20 °C → P ≈ 255 kW. With higher flow and wider ΔT, capacity scales linearly up to the plate area limit.
Standard (no "H") plate profile — balanced heat transfer and pressure drop, suited for typical heating/cooling applications.
Yes. Hexonic LB60 series is compatible with ethylene glycol and propylene glycol solutions at standard concentrations, when appropriate inhibitors are used. For DHW — only potable-grade fluids allowed.
Brazed gasket-free construction requires no periodic disassembly maintenance. Recommended only CIP (Clean-in-Place) flushing periodically if fouling signs appear (rising pressure drop or falling heat transfer).
Not in all cases. Hexonic states that the standard copper-brazed L series should not be treated as a universally suitable solution for direct contact with potable water — acceptability depends on local requirements and approvals. For potable water Hexonic recommends SafePLATE (double-wall design) or the all-stainless-steel LUNA series.
In some regions, district heating water contains elevated chlorides or ammonia — in such systems, copper brazing may shorten service life. In these cases we recommend the Danfoss XB CoResist series or gasketed plate exchangers with EPDM/NBR gaskets. For hard water with elevated Ca/Mg carbonate content, limescale gradually builds up on the plates and reduces heat-transfer efficiency; for such systems gasketed (plate-and-frame) exchangers are preferable, as they can be periodically opened for mechanical or CIP cleaning. Contact us — we will select the model best suited to your water conditions.
In heating systems where heat losses to the room should be minimized, the APFI series insulation shell is recommended (polyurethane foam with aluminum cover, up to 135 °C). In substations, insulation is nearly a default choice.