Hexonic LC110 — C size (larger than B) plate exchanger, plates ~466 × 258 mm. The 40-plate pack is used in large-capacity central heating substations, industrial heat recovery processes, chiller primary loop separation, commercial buildings, and large-scale district heating consumer stations. G 2" connections support high flow rates (up to ~20-25 m³/h).
| Parameter | Value |
|---|---|
| Code | 0206-0274 |
| Series | Hexonic LC110 |
| Model | LC110-40-2 |
| Number of plates | 40 |
| Passes | 1 (1-pass, 4 connections) |
| Nominal pressure (PN) | 25 bar |
| Max working temperature | 230 °C |
| Min working temperature | -195 °C |
| Connection | G 2" external thread |
| Plate material | Stainless steel AISI 316L (1.4404) |
| Brazing filler | Copper (Cu) |
| Plate dimensions | 466 × 258 mm |
| Unit depth (F) | ~107.0 mm (formula: 11 + 2.4 × N, N = 40) |
| Weight | ~25 kg |
| Construction | Brazed, hermetic (gasket-free) |
| Media | Water, glycol solutions up to 50 % |
General formula: P = Q × ΔT × 1.163 (kW, Q m³/h, ΔT °C). LC110 plates are sized for higher flows — G 2" connections handle up to ~25 m³/h of water with acceptable Δp.
Example for heating mode (primary 90/70 °C → secondary 65/40 °C): at Q ≈ 12.0 m³/h and effective ΔT ≈ 20 °C → P ≈ 280 kW. At 25 °C ΔT, capacity scales proportionally.
Official Hexonic catalogue: hexonic.com/brazed-plate-exchangers/L
LC110 has larger plate area (~466 × 258 mm), designed for higher flows and higher capacity. LB60 — mid-capacity, more compact, G 5/4" connections. Choose LC110 when capacity is >250 kW or flow >10 m³/h.
Yes, up to 50 % ethylene or propylene glycol with appropriate inhibitors.
Brazed construction — no disassembly needed. CIP flushing every 3-5 years if fouling signs appear.
Yes. AISI 316L plates and copper brazing meet WRAS/DVGW requirements.
APFI series insulation shell is recommended — fits LC110 plate count groups (10-20, 21-40, 41-60, 61-80, 81-100).