This 50-plate brazed heat exchanger with LC110 plates and 2-pass (2S) configuration is designed for medium-to-high capacity heating and DHW systems — commercial buildings, production facilities, boiler-room primary/secondary circuits. Plate size ~466 × 258 mm, 2" connections. The 2-pass configuration with 6 connections (Hexonic designation "2S") provides additional connections for the central heating return and domestic hot water circulation return (per the manufacturer catalogue).
| Parameter | Value |
|---|---|
| Code | 0206-0293 |
| Series | Hexonic LC110 |
| Model | LC110-50-2S-2 |
| Number of plates | 50 |
| Configuration | 2-pass (2S), 6 connections |
| Nominal pressure (PN) | 25 bar (2.5 MPa) |
| Connection | G 2" external thread |
| Plate material | Stainless steel AISI 316L |
| Brazing material | Copper |
| Working temperature range | −195 °C … +230 °C |
| Dimensions (W × D × H) | 258 × 131.0 × 466 mm (W × D × H) |
| Weight (approx.) | ~31.6 kg |
| Construction | Vacuum-furnace brazed, hermetic (gasket-free) |
| Media | Water, inhibited propylene and ethylene glycol solutions at standard concentrations (confirm the exact concentration with the manufacturer) |
Capacity depends on flow rate, ΔT and logarithmic mean temperature difference (LMTD). General formula: P = Q × ΔT × 1.163 (kW, where Q — m³/h, ΔT — °C).
Illustrative calculation, not this model's capacity. Example for typical heating duty (primary 90/70 °C → secondary 65/40 °C): at Q = 4.3 m³/h and effective ΔT ≈ 25 °C → P ≈ 125 kW. Final sizing is determined by design conditions and Hexonic CAIRO selection software.
Yes, with inhibited propylene and ethylene glycol solutions at standard concentrations. The manufacturer does not state a maximum concentration — confirm with Hexonic. For DHW systems, only potable-grade fluids are allowed.
Brazed gasket-free construction requires no periodic disassembly maintenance. Recommended only CIP (Clean-in-Place) flushing periodically if fouling signs appear (rising pressure drop or falling heat transfer). Suitable CIP reagents — mild acid solutions (e.g., citric, sulfamic acid) followed by neutralization and rinsing.
The standard Hexonic L-series exchanger with copper brazing is not considered universally suitable for direct contact with potable water — acceptability depends on local requirements and approvals. For such use the manufacturer recommends SafePLATE (double-wall) or the all-stainless-steel LUNA series.
In some regions, district-heating water contains elevated chlorides or ammonia — in such systems, copper brazing may shorten the service life of the exchanger. In these cases we recommend the Danfoss XB CoResist series. For hard water with elevated Ca/Mg carbonate content, limescale gradually builds up on the plates and reduces heat-transfer efficiency; for such systems gasketed (plate-and-frame) exchangers are preferable, as they can be periodically opened for mechanical or CIP cleaning. Contact us — we will select the model best suited to your water conditions.