Hexonic LC110 — C size (larger than B) plate exchanger, plates ~466 × 258 mm. The 60-plate pack is used in large-capacity central heating substations, industrial heat recovery processes, chiller primary loop separation, commercial buildings, and large-scale district heating consumer stations. G 2" connections are intended for higher flow rates.
| Parameter | Value |
|---|---|
| Code | 0206-0276 |
| Series | Hexonic LC110 |
| Model | LC110-60-2 |
| Number of plates | 60 |
| Passes | 1 (1-pass, 4 connections) |
| Nominal pressure (PN) | 25 bar |
| Max working temperature | 230 °C |
| Min working temperature | -195 °C |
| Connection | G 2" external thread |
| Plate material | Stainless steel AISI 316L (1.4404) |
| Brazing filler | Copper (Cu) |
| Plate dimensions | 466 × 258 mm |
| Unit depth (F) | ~155.0 mm (formula: 11 + 2.4 × N, N = 60) |
| Weight | ~35.1 kg |
| Construction | Brazed, hermetic (gasket-free) |
| Media | Water, inhibited propylene and ethylene glycol solutions at standard concentrations (confirm the exact concentration with the manufacturer) |
General formula: P = Q × ΔT × 1.163 (kW, Q m³/h, ΔT °C). LC110 plates are sized for higher flows; verify flow and Δp limits with Hexonic CAIRO.
Illustrative calculation, not this model's capacity. Example for heating mode (primary 90/70 °C → secondary 65/40 °C): at Q ≈ 18.1 m³/h and effective ΔT ≈ 20 °C → P ≈ 420 kW. At 25 °C ΔT, capacity scales proportionally.
Hexonic manufacturer's catalogue: hexonic.com/brazed-plate-exchangers/L
LC110 has larger plate area (~466 × 258 mm) and 2" connections, designed for higher flows and higher capacity. LB60 — smaller plate (~538 × 123 mm), connections 3/4"–5/4", PN 30.
Yes, with inhibited propylene and ethylene glycol solutions at standard concentrations. The manufacturer does not state a maximum concentration — confirm with Hexonic.
Brazed construction — no disassembly needed. CIP flushing periodically if fouling signs appear (per the manufacturer's CIP instructions).
The standard Hexonic L-series exchanger with copper brazing is not considered universally suitable for direct contact with potable water — acceptability depends on local requirements and approvals. For such use the manufacturer recommends SafePLATE (double-wall) or the all-stainless-steel LUNA series.
APFI series insulation shell is recommended — fits LC110 plate count groups (10-20, 21-40, 41-60, 61-80, 81-100).