-44%
Hexonic LC110-60-2S-2 brazed plate heat exchanger, 60 plates, PN 25

Hexonic LC110-60-2S-2 brazed plate heat exchanger, 60 plates, PN 25

€ 1430,80€ 2555,00+ PVM
SKU
0206-0294
Model
LC110-60-2S-2
Delivery
1 - 2 working days.
Brand
Hexonic
used_for
silumokaitis_karstam_vandeniui
Connection Type
iorsriegis_dn50
Number Of Plates
60
Connection nozzles
6
degrees
2
product_analogue
xb52m23030
operating_pressure
25
Weight
33.2kg.
Have questions?
TL;DR: Hexonic LC110-60-2S-2 — high-capacity brazed plate heat exchanger with 60 stainless steel (AISI 316L) plates, copper brazing and 2-pass (2S) configuration. Designed for HVAC heating, cooling and domestic hot water (DHW) production.
  • Application: heating/cooling/DHW primary–secondary loop separation
  • Heat capacity: depends on flow rates, temperatures and number of plates (select with Hexonic CAIRO)
  • Nominal pressure: PN 25 (2.5 MPa)
  • Connection: G 2" external thread (both sides)

Where LC110-60 is used

This 60-plate brazed heat exchanger with LC110 plates and 2-pass (2S) configuration is designed for medium-to-high capacity heating and DHW systems — commercial buildings, production facilities, boiler-room primary/secondary circuits. Plate size ~466 × 258 mm, 2" connections. The 2-pass configuration with 6 connections (Hexonic designation "2S") provides additional connections for the central heating return and domestic hot water circulation return (per the manufacturer catalogue).

Technical specifications

Parameter Value
Code0206-0294
SeriesHexonic LC110
ModelLC110-60-2S-2
Number of plates60
Configuration2-pass (2S), 6 connections
Nominal pressure (PN)25 bar (2.5 MPa)
ConnectionG 2" external thread
Plate materialStainless steel AISI 316L
Brazing materialCopper
Working temperature range−195 °C … +230 °C
Dimensions (W × D × H)258 × 155.0 × 466 mm (W × D × H)
ConstructionVacuum-furnace brazed, hermetic (gasket-free)
MediaWater, inhibited propylene and ethylene glycol solutions at standard concentrations (confirm the exact concentration with the manufacturer)

Heat transfer capacity — quick calculation

Capacity depends on flow rate, ΔT and logarithmic mean temperature difference (LMTD). General formula: P = Q × ΔT × 1.163 (kW, where Q — m³/h, ΔT — °C).

Illustrative calculation, not this model's capacity. Example for typical heating duty (primary 90/70 °C → secondary 65/40 °C): at Q = 5.2 m³/h and effective ΔT ≈ 25 °C → P ≈ 150 kW. Final sizing is determined by design conditions and Hexonic CAIRO selection software.

Designer note: Before final sizing, run a calculation via Hexonic CAIRO Selection Software or request Amegata technical consultation — we will select the right model based on your flow rates and ΔT.

When to choose LC110-60

  • Heating/cooling primary–secondary loop separation
  • Domestic hot water (DHW) primary heat exchanger
  • Cooling systems buffer separation (chilled water primary / building loop secondary)
  • When gasket-free hermetic construction is required
  • Water and inhibited glycol solution systems

B2B delivery and logistics via Amegata.lt

  • 24-hour delivery across Lithuania (from our warehouse in Vilnius)
  • Competitive B2B pricing — often below market average
  • 30-day payment terms for companies (per contract)
  • Free technical consultation for sizing and CAIRO calculation

Frequently asked questions

Is it suitable for ethylene glycol and propylene glycol solutions?

Yes, with inhibited propylene and ethylene glycol solutions at standard concentrations. The manufacturer does not state a maximum concentration — confirm with Hexonic. For DHW systems, only potable-grade fluids are allowed.

What maintenance is required?

Brazed gasket-free construction requires no periodic disassembly maintenance. Recommended only CIP (Clean-in-Place) flushing periodically if fouling signs appear (rising pressure drop or falling heat transfer). Suitable CIP reagents — mild acid solutions (e.g., citric, sulfamic acid) followed by neutralization and rinsing.

Is it suitable for potable water (DHW)?

The standard Hexonic L-series exchanger with copper brazing is not considered universally suitable for direct contact with potable water — acceptability depends on local requirements and approvals. For such use the manufacturer recommends SafePLATE (double-wall) or the all-stainless-steel LUNA series.

Is it suitable for aggressive water with chlorides or ammonia?

In some regions, district-heating water contains elevated chlorides or ammonia — in such systems, copper brazing may shorten the service life of the exchanger. In these cases we recommend the Danfoss XB CoResist series. For hard water with elevated Ca/Mg carbonate content, limescale gradually builds up on the plates and reduces heat-transfer efficiency; for such systems gasketed (plate-and-frame) exchangers are preferable, as they can be periodically opened for mechanical or CIP cleaning. Contact us — we will select the model best suited to your water conditions.