-44%
Hexonic LC110-90-2 brazed plate heat exchanger, 2", 90 plates, PN 25

Hexonic LC110-90-2 brazed plate heat exchanger, 2", 90 plates, PN 25

€ 1773,00€ 3145,00+ PVM
SKU
0206-0279
Model
LC110-90-2
Delivery
1 - 2 working days.
Brand
Hexonic
used_for
silumokaitis_sildymui
Connection Type
iorsriegis_dn50
Number Of Plates
90
assembly_length
227
Connection nozzles
4
degrees
1
operating_pressure
25
Weight
47.4kg.
Have questions?
TL;DR: Hexonic LC110-90-2 — high-capacity brazed plate heat exchanger with 90 stainless steel AISI 316L plates and copper brazing. LC110 series, single-pass construction with G 2" connections. Designed for large substations, commercial buildings, and industrial processes.
  • Application: large substations, industrial processes, chillers
  • Heat capacity: depends on flow rates, temperatures and number of plates (select with Hexonic CAIRO)
  • Nominal pressure: PN 25 (25 bar)
  • Connection: G 2" external threads

Where LC110-90-2 is used

Hexonic LC110 — C size (larger than B) plate exchanger, plates ~466 × 258 mm. The 90-plate pack is used in large-capacity central heating substations, industrial heat recovery processes, chiller primary loop separation, commercial buildings, and large-scale district heating consumer stations. G 2" connections are intended for higher flow rates.

Technical specifications

ParameterValue
Code0206-0279
SeriesHexonic LC110
ModelLC110-90-2
Number of plates90
Passes1 (1-pass, 4 connections)
Nominal pressure (PN)25 bar
Max working temperature230 °C
Min working temperature-195 °C
ConnectionG 2" external thread
Plate materialStainless steel AISI 316L (1.4404)
Brazing fillerCopper (Cu)
Plate dimensions466 × 258 mm
Unit depth (F)~227.0 mm (formula: 11 + 2.4 × N, N = 90)
Weight~47.4 kg
ConstructionBrazed, hermetic (gasket-free)
MediaWater, inhibited propylene and ethylene glycol solutions at standard concentrations (confirm the exact concentration with the manufacturer)

Heat transfer capacity — quick calculation

General formula: P = Q × ΔT × 1.163 (kW, Q m³/h, ΔT °C). LC110 plates are sized for higher flows; verify flow and Δp limits with Hexonic CAIRO.

Illustrative calculation, not this model's capacity. Example for heating mode (primary 90/70 °C → secondary 65/40 °C): at Q ≈ 27.1 m³/h and effective ΔT ≈ 20 °C → P ≈ 630 kW. At 25 °C ΔT, capacity scales proportionally.

Designer note: LC110 series — larger plate area, suited for high capacity at moderate Δp. For higher capacities Hexonic offers larger sizes (e.g., LC170). The PN 25 bar limit is critical for district heating networks with potential water hammer — assess hydraulic transients.

When to choose LC110-90-2

  • Large-capacity substations
  • Industrial process heat recovery
  • Chiller cooling system buffer separation
  • When flows require G 2" connections and pressure stays under 25 bar

When to choose an alternative

  • Pressure above 25 bar → LM110 (up to 30 bar) or a solution agreed with the manufacturer
  • Higher flows → a larger size (e.g., LC170)

B2B delivery and logistics via Amegata.lt

  • 24-hour delivery across Lithuania (from our warehouse in Vilnius)
  • Larger LC110 units (90+ plates) are often made-to-order — we will confirm lead time
  • 30-day payment terms for companies (per contract)
  • Free technical consultation for sizing selection

Hexonic manufacturer's catalogue: hexonic.com/brazed-plate-exchangers/L

Frequently asked questions

How does LC110 differ from LB60?

LC110 has larger plate area (~466 × 258 mm) and 2" connections, designed for higher flows and higher capacity. LB60 — smaller plate (~538 × 123 mm), connections 3/4"–5/4", PN 30.

Can glycol mixtures be used?

Yes, with inhibited propylene and ethylene glycol solutions at standard concentrations. The manufacturer does not state a maximum concentration — confirm with Hexonic.

What maintenance is required?

Brazed construction — no disassembly needed. CIP flushing periodically if fouling signs appear (per the manufacturer's CIP instructions).

Is it suitable for potable water?

The standard Hexonic L-series exchanger with copper brazing is not considered universally suitable for direct contact with potable water — acceptability depends on local requirements and approvals. For such use the manufacturer recommends SafePLATE (double-wall) or the all-stainless-steel LUNA series.

Is insulation needed?

APFI series insulation shell is recommended — fits LC110 plate count groups (10-20, 21-40, 41-60, 61-80, 81-100).

  • About us

  • HELP AND INFORMATION

  • CONNECT WITH US

Notify me of new products
By clicking the "Subscribe" button, you agree to the Privacy Policy. You will always find a link in the newsletter that you can click to unsubscribe from.

@ 2024-2026. All rights reserved.

    Solution: e-bros