Honeywell T7425A1005 is the primary immersion sensor for Honeywell HVAC control schemes. Used for: heating flow/return temperature, DHW supply temperature after the heat exchanger, DH return-line measurement, boiler-room outlet monitoring. The 75 mm probe suits DN 20–50 pipework. Compatible with Honeywell Excel 5000, Excel 500, Centraline Falcon and other platforms reading the Honeywell NTC 20 kΩ standard. Delivery across the EU.
| Parameter | Value |
|---|---|
| Code | T7425A1005 (VFF20-75P65) |
| Model | Honeywell VFF20-75P65 |
| Sensor type | NTC thermistor, 20 kΩ (25 °C) |
| Mounting | Immersion in a pocket (G ½") |
| Probe length | 75 mm |
| Probe diameter | Ø 6 mm |
| Measurement range | -20 → +140 °C |
| Accuracy | ±0.4 °C (0 → +100 °C), ±0.8 °C over the remainder |
| Time constant | ≈ 20 s (in pocket) / ≈ 8 s (direct in liquid) |
| Probe material | Stainless steel AISI 316 |
| Wiring | 2-wire, terminals in the sensor head |
| Protection class | IP65 (head) |
| Compatibility | Honeywell Excel 5000, Excel 500, Centraline Falcon and other NTC 20 kΩ controllers |
T7425A1005 uses NTC 20 kΩ (Honeywell's standard — NOT 10 kΩ Ouman, NOT 1.8 kΩ Schneider EGU). Verify controller documentation before replacing a sensor. The 75 mm probe suits DN 20–50 pipework — pocket active length should be 55–65 mm so the tip sits at the flow centre. Fill the pocket with heat-transfer paste or silicone oil.
Official Honeywell catalog: buildings.honeywell.com
No. T7425A1005 uses NTC 20 kΩ. Ouman reads NTC 10 kΩ, Danfoss ECL reads PT1000, Schneider TAC reads NTC 1.8 kΩ. These standards are not interchangeable — verify the controller documentation first.
An NTC 20 kΩ element reads roughly 5.3 kΩ at 60 °C; ~25 kΩ at 20 °C; 20 kΩ at 25 °C (nominal). A multimeter check confirms operation.
Standard orders require the pocket to be ordered separately — a Honeywell or third-party G ½" pocket with 55–65 mm active length. Contact us — we will match it to your pipe diameter and pressure class.
Standard 2-wire line up to 100 m of unshielded 2×1.5 mm² cable. Shielded twisted pair for longer runs or high-EMI environments. NTC signals are tolerant of cable resistance and remain undistorted.
The number before P65 encodes probe length; VFF20 = 75 mm, VFF10 = 100 mm on some variants. P65 refers to the IP65 rating. Choose based on pipe diameter and ambient conditions.