Applied for hydraulic balancing of small consumer branches — floor-level heating risers in 2-3 storey multi-family buildings, apartment metering schemes with thermostatic heads, small cooling zones in commercial buildings. DA-616 automatically holds a constant Δp across the controlled branch — so thermostatic valves see a stable pressure drop and operate at a consistent characteristic point, regardless of other consumer activity in the system.
| Parameter | Value |
|---|---|
| Code | 52-861-015 |
| Series | IMI TA Hydronics DA-616 |
| Type | Automatic differential pressure (Δp) controller |
| DN | 15 |
| Kvs | 5 m³/h |
| Nominal pressure (PN) | 16 bar (verify in IMI catalogue) |
| Δp setting range | Per variant (typically 5-30 kPa or 10-60 kPa — see IMI documentation) |
| Connection | Internal thread (Rp) |
| Temperature range | -10 → +120 °C |
| Media | Heating/cooling water, glycol up to 50 % |
| Body material | DZR brass / bronze (per IMI documentation) |
| Capillary tube | Ordered separately (code 52-850-915 or equivalent) |
Water flow through the valve: Q = Kvs × √Δp (Δp in bar; Q in m³/h). Heat capacity: P = Q × ΔT × 1.163 (kW, ΔT °C, Q m³/h).
Example: setting Δp = 0.3 bar (30 kPa) → Q = 5 × √0.3 ≈ 2.74 m³/h. With ΔT = 15 °C → P ≈ 48 kW.
Official IMI Hydronic catalogue: imi-hydronic.com
Functionally equivalent: both are proportional automatic Δp controllers on the consumer branch. Differences: IMI TA Hydronics uses different capillary connections, diaphragm construction and Δp range classes. In practice, one can substitute the other at the same Kvs.
Yes. DA-616 operates hydraulically — a capillary tube is essential (IMI TA Hydronics 52-850-915 or equivalent) to transmit the pressure signal from the consumer branch. The capillary is not included in the package.
Yes. IMI Hydronics allows use with ethylene or propylene glycol solutions up to 50 %, with proper inhibitors.
The Δp setpoint must match the design pressure drop of the thermostatic valves plus the branch pressure losses. For a domestic branch with thermostatic heads, typical settings are 10-20 kPa (0.1-0.2 bar). Higher settings risk noise and cavitation in the valves.