For high-load heating headers — commercial buildings (offices, shopping centres), high-rise residential heating branches, schools and hotels with combined building heat load up to ~250 kW. Provides stable Δp across a large consumer network when load is distributed among many users with varying operating patterns.
| Parameter | Value |
|---|---|
| Code | 52-861-032 |
| Series | IMI TA Hydronics DA-616 |
| Type | Automatic differential pressure (Δp) controller |
| DN | 32 |
| Kvs | 15 m³/h |
| Nominal pressure (PN) | 16 bar (verify in IMI catalogue) |
| Δp setting range | Per variant — see IMI documentation |
| Connection | Internal thread (Rp) |
| Temperature range | -10 → +120 °C |
| Media | Heating/cooling water, glycol up to 50 % |
| Body material | DZR brass / bronze (per IMI documentation) |
| Capillary tube | Ordered separately (52-850-915 or equivalent) |
Water flow: Q = Kvs × √Δp. Heat capacity: P = Q × ΔT × 1.163.
Example: setting Δp = 0.3 bar (30 kPa) → Q = 15 × √0.3 ≈ 8.22 m³/h. With ΔT = 20 °C → P ≈ 191 kW.
Official IMI Hydronic catalogue: imi-hydronic.com
When calculated flow at the target Δp exceeds DN25 Kvs 10 capacity. Example: if desired flow is 6 m³/h at Δp = 20 kPa, DN25 provides only 10 × √0.2 ≈ 4.47 m³/h (insufficient). DN32 with Kvs 15 provides 15 × √0.2 ≈ 6.7 m³/h — meets the requirement. Otherwise DN32 is oversized.
Only on the secondary side after the heat exchanger (building side). The primary DH supply side (before the exchanger) requires different Δp regulators with higher working pressure and temperature — e.g. PICV combined with temperature limiting.
Theoretically possible, practically uneconomical. Better solution — a larger Kvs valve or a dedicated high-load DN solution. Parallel units may require additional synchronisation and more complex hydraulic layout.
In cooling systems (media below room temperature) condensate-prevention insulation is essential. In heating systems insulation is recommended per energy regulations — typically 25-40 mm mineral wool with vapour barrier.