High-load commercial complexes, spa hotels, industrial sites, large sports centres. High-power boiler-house heating loops with hydraulic separation. Delivery across the EU.
| Parameter | Value |
|---|---|
| Code | 004H4528 |
| Plate count | 80 |
| Hydraulic layout | 1-pass |
| Connections | G 1 1/2" male thread |
| Max pressure | 25 bar |
| Temperature range | −10 → 195 °C |
| Plates | AISI 316 |
| Braze | Copper |
Series maximum — validate sizing via Danfoss HExact before ordering. For > 550 kW or flow > 15 m³/h consider a dismountable plate exchanger for long-term maintainability.
Official Danfoss catalog: store.danfoss.com/004H4528
Add 10-15 % reserve depending on water quality. Industrial sites — add 20 % for scaling/fouling.
The system needs air separators (Reflex Flamco Airex or similar) — plate exchangers do not tolerate air accumulation.