Small-load heating loops, DHW branches, small substation consumer circuits. Kvs 2.5 fits flows up to ~30 kW (ΔT 20 °C). Combined with a modulating actuator (AMV 435 or AMV 20/25) driven by ECL Comfort. Delivery across the EU.
| Parameter | Value |
|---|---|
| Code | 065F2115 |
| Type | Two-way seat control valve |
| DN | 15 |
| Kvs | 2.5 m³/h |
| PN | 25 bar |
| Connection | Rp 1/2" female thread |
| Temperature range | 2 → 150 °C |
| Media | Heating water, glycol up to 50 % |
| Stroke | up to 15 mm |
| Characteristic | Equal percentage (logarithmic) |
| Leakage class | IV (0.05 % Kvs) |
| Body material | Red bronze |
| Compatible actuators | AMV 20, AMV 25, AMV 30, AMV 435 |
Flow: Q = Kvs × √Δp. Power: P = Q × ΔT × 1.163. Example: Δp = 0.3 bar → Q ≈ 1.37 m³/h; ΔT 20 °C → P ≈ 32 kW.
Size VS2 by Kvs, not by DN. Valve authority β = Δp_valve / Δp_loop must be ≥ 0.5. Oversized Kvs → poor authority → unstable control. VS2 is often paired with an AVP differential-pressure controller on the branch.
Official Danfoss catalog: store.danfoss.com/065F2115
AMV 435 (0-10 V / 3-pt) is the standard choice. Alternative: AMV 20/25 for 3-point control.
Yes. VS2 handles DHW flow control up to 150 °C and PN 25 bar.
VS2 — DN15-25 threaded, for smaller loops. VM2 — DN25-40, for larger flows, also threaded.