Flamco T-Plus DN25 rapid installation tee for steel pipes, Rp 3/4" branch, PN 25

Flamco T-Plus DN25 rapid installation tee for steel pipes, Rp 3/4" branch, PN 25

€ 170,73+ PVM
SKU
90626
Model
T Plius Dn25x3/4``
Delivery
1 - 2 working days.
Brand
flamco
Weight
1.33kg.
Have questions?
TL;DR: Flamco T-Plus DN25 — cast iron rapid installation tee, clamped onto a DN25 (Ø 33.7 mm) steel pipe to form an Rp 3/4" branch. Designed for apartment supply branches and small manifold feeds without stopping system operation.
  • Application: DN20 branch on a DN25 steel pipe
  • Pipe outer Ø: 33.7 mm (1")
  • Branch connection: Rp 3/4" (female thread, DN20)
  • Nominal pressure / T: PN 25 / +120 °C

Where T-Plus DN25 is used

DN25 is typically chosen for apartment heating branches in multi-family buildings and for feeding small underfloor heating manifolds. When a DN25 main riser needs to be tapped into — for example, to install a separate metering unit (energy meter) for an apartment or to connect an additional underfloor heating loop — the T-Plus allows this without shutting down the whole riser.

The 16 Nm tightening torque is achievable with a standard torque wrench. The joint withstands classic district heating pressure and temperature, so it works on both flow and return lines. Installation time about 5-7 minutes, no drain-down and refill cycle.

Technical specifications

Parameter Value
Code90626
SeriesFlamco T-Plus, cast iron version
ModelT-Plus DN25 x Rp 3/4"
Pipe nominal DNDN25 (1")
Pipe outer Ø33.7 mm
Branch connectionRp 3/4" (BSP female thread, DN20)
Housing materialCast iron with anti-corrosion coating
SealEPDM with single-use cutting element
Max working pressurePN 25 (25 bar)
Max working T+120 °C
Permissible pipe wall thickness≤ 2.0 mm
Tightening torque16 Nm
Pipe standardsDIN EN 10255 (Series M/H), DIN EN 10216, DIN EN 10217
MediaHeating water, chilled water, potable water, solar, compressed air
InstallationClamp-on with system in operation, no welding, no threading
Designer note: for metering unit installation on a DN25 riser, the T-Plus allows fitting an additional shut-off valve and meter without shutting down the whole riser — important when tenant consent to riser shutdown is difficult to organise in apartment buildings. Make sure the Rp 3/4" branch has a small-mesh strainer and ball valve installed upstream of the meter — otherwise the meter warranty may be void.

When to choose T-Plus DN25

  • Apartment heating branch on a DN25 riser in multi-family buildings
  • Individual metering unit (energy meter) installation without riser shutdown
  • Small underfloor heating manifold feed branching
  • Compatibility: steel pipes per DIN EN 10255 M/H, DIN EN 10216, DIN EN 10217 with wall thickness ≤ 2.0 mm

B2B delivery and logistics via Amegata.lt

  • 24-hour delivery across Lithuania (from our warehouse in Vilnius)
  • Competitive B2B pricing — often below market average
  • 30-day payment terms for companies (per contract)
  • Free technical consultation on pipe compatibility

Official Flamco catalogue: flamco.aalberts-hfc.com/T-plus 90626

Frequently asked questions

Is a special tool required for T-Plus installation?

No. A torque wrench (16 Nm) and free access to the pipe (~150 mm around the clamp point) is enough. No drilling, welding or threading equipment needed — the cutting element pierces the pipe as the bolts are tightened.

Can it be used with an energy meter (metering unit)?

Yes. The T-Plus DN25 is commonly used for apartment metering unit installation — the Rp 3/4" branch allows a ball valve, strainer and DN20 or DN15 heat meter to be connected downstream. Confirm meter inlet/outlet sizes with the meter supplier before installation.

How to prepare the pipe before installation?

The pipe surface at the clamp point must be clean (no paint, rust scale or insulation). Verify the wall thickness ≤ 2.0 mm. Thicker walls (heavy-series steel pipes) are not compatible with T-Plus.

Can it be used in chilled water (chiller) systems?

Yes, the manufacturer confirms cooling system use. For long-term operation with condensation forming — make sure the housing and clamp point are insulated from ambient air to prevent local corrosion.