DN25 is typically chosen for apartment heating branches in multi-family buildings and for feeding small underfloor heating manifolds. When a DN25 main riser needs to be tapped into — for example, to install a separate metering unit (energy meter) for an apartment or to connect an additional underfloor heating loop — the T-Plus allows this without shutting down the whole riser.
The 16 Nm tightening torque is achievable with a standard torque wrench. The joint withstands classic district heating pressure and temperature, so it works on both flow and return lines. Installation time about 5-7 minutes, no drain-down and refill cycle.
| Parameter | Value |
|---|---|
| Code | 90626 |
| Series | Flamco T-Plus, cast iron version |
| Model | T-Plus DN25 x Rp 3/4" |
| Pipe nominal DN | DN25 (1") |
| Pipe outer Ø | 33.7 mm |
| Branch connection | Rp 3/4" (BSP female thread, DN20) |
| Housing material | Cast iron with anti-corrosion coating |
| Seal | EPDM with single-use cutting element |
| Max working pressure | PN 25 (25 bar) |
| Max working T | +120 °C |
| Permissible pipe wall thickness | ≤ 2.0 mm |
| Tightening torque | 16 Nm |
| Pipe standards | DIN EN 10255 (Series M/H), DIN EN 10216, DIN EN 10217 |
| Media | Heating water, chilled water, potable water, solar, compressed air |
| Installation | Clamp-on with system in operation, no welding, no threading |
Official Flamco catalogue: flamco.aalberts-hfc.com/T-plus 90626
No. A torque wrench (16 Nm) and free access to the pipe (~150 mm around the clamp point) is enough. No drilling, welding or threading equipment needed — the cutting element pierces the pipe as the bolts are tightened.
Yes. The T-Plus DN25 is commonly used for apartment metering unit installation — the Rp 3/4" branch allows a ball valve, strainer and DN20 or DN15 heat meter to be connected downstream. Confirm meter inlet/outlet sizes with the meter supplier before installation.
The pipe surface at the clamp point must be clean (no paint, rust scale or insulation). Verify the wall thickness ≤ 2.0 mm. Thicker walls (heavy-series steel pipes) are not compatible with T-Plus.
Yes, the manufacturer confirms cooling system use. For long-term operation with condensation forming — make sure the housing and clamp point are insulated from ambient air to prevent local corrosion.