DN65 typically features in commercial building and multi-family main heating/cooling networks — buffer manifolds, townhouse distribution loops, office substation nodes. T-Plus DN65 lets you add a user branch or technical module (extra pump, sensor pocket, mainline filter, DHW module) without pressure loss or welding.
| Parameter | Value |
|---|---|
| Code | 90665 |
| Manufacturer | Flamco (Aalberts HFC) |
| Series | T-plus cast iron |
| Nominal pipe diameter | DN65 (2½") |
| Branch connection | Rp 1¼" (female thread) |
| Nominal pressure PN | 25 bar |
| Max operating temperature | 130 °C |
| Body material | Cast iron with anti-corrosion coating |
| Compatible pipes | Steel (St33/34/35/37) per DIN 2441 / NEN 3257 C Heavy / BS 1387 Heavy |
| Wall thickness (steel DN65) | ~4.0-4.5 mm (Heavy grade) |
| Media | Water, glycol solutions up to 50 %, compressed air |
| Piercing mechanism | Single-shot, integrated |
Official Flamco catalogue: flamcogroup.com/T-plus
T-Plus targets branches with flow much smaller than the main. Rp 1¼" (Kvs ≈ 25-30 m³/h) covers most user branches, measurement points, and secondary loops. For larger tap-ins, use a shutdown-and-weld tee.
Yes. Recommended orientation — branch pointing up or sideways (12 / 3 / 9 o'clock). Avoid downward (6 o'clock) orientation — sludge and deposits accumulate in the branch opening.
Yes, up to 50 % ethylene or propylene glycol with proper inhibitors.
Installed T-Plus needs no periodic service. Annual visual check recommended (corrosion, leak signs).
Yes, up to 130 °C and 25 bar. Higher-parameter DH lines (150+ °C) require a higher-rated solution — contact us.