DN32 is typically chosen for floor or section riser branching, manifold feed points and additional heating loop connection (e.g. underfloor). This size is popular on the consumer side of multi-family substations, where several apartment or underfloor loop branches need to be led off a DN32 main manifold.
The 16 Nm tightening torque is achievable with a torque wrench and a normal arm extension. Where the same job with welding and a drain-down cycle would take 4-6 hours with a shutdown that is impossible during the heating season, the T-Plus completes it in about 10 minutes without disrupting existing users.
| Parameter | Value |
|---|---|
| Code | 90632 |
| Series | Flamco T-Plus, cast iron version |
| Model | T-Plus DN32 x Rp 1" |
| Pipe nominal DN | DN32 (1 1/4") |
| Pipe outer Ø | 42.4 mm |
| Branch connection | Rp 1" (BSP female thread, DN25) |
| Housing material | Cast iron with anti-corrosion coating |
| Seal | EPDM with single-use cutting element |
| Max working pressure | PN 25 (25 bar) |
| Max working T | +120 °C |
| Permissible pipe wall thickness | ≤ 2.0 mm |
| Tightening torque | 16 Nm |
| Pipe standards | DIN EN 10255 (Series M/H), DIN EN 10216, DIN EN 10217 |
| Media | Heating water, chilled water, potable water, solar, compressed air |
| Installation | Clamp-on with system in operation, no welding, no threading |
Official Flamco catalogue: flamco.aalberts-hfc.com/T-plus 90632
Up to +120 °C and PN 25 (25 bar). Withstands classic district heating regimes (90/70 °C) and individual boiler house pressures. Higher temperatures (steam) and higher pressures — not suitable.
No. A 16 Nm torque wrench and free pipe access (~200 mm around the clamp point). The cutting element pierces the pipe as the bolts are tightened — no drilling equipment or welding gear needed.
Yes, the manufacturer confirms cooling system use. For long-term operation with condensation forming, make sure the housing and clamp point are insulated from ambient air.
The pipe surface at the clamp point must be clean (no paint, rust scale or insulation). Verify the wall thickness ≤ 2.0 mm. Thicker pipes (heavy-series steel) are not compatible with T-Plus.